No products in the cart.
Zeta Infinity 8-IN2 | 2 Zone Conventional Fire Alarm Panel
Call for Price
- Brand : ZETA
- Model : Infinity 8 – IN2
- Country of Origin: UK
- Access via password – removes problem of lost keys
- One man test facility
- Disablement facility for zones & sounders
- Space for up to 3Ah batteries
- Sounder delay option
- 4 sounder circuits (IN4, IN6 & IN8)
- Sounder circuits 3 and/or 4 can be configured as Aux 24V supplies
- Meets all requirements of latest EN54 part 2 and part4
Zeta Infinity 8-IN2 | 2 Zone Conventional Fire Alarm Panel in Bangladesh
The Infinity 8 control panel is housed in the most attractive, modern designed, flame retardant ABS enclosure, utilizing a switch mode power supply. It has a fully removable front cover which improves ease of access for cable installations.

ZETA Fire Alarm Bangladesh, Zeta Infinity 8-IN2 | 2 Zone Conventional Fire Alarm Panel in Bangladesh
Technical Specifications:
Model | IN1 | IN2 | IN4 | IN6 | IN8 |
Part No | 37-650 | 37-651 | 37-652 | 37-653 | 37-654 |
Mains Voltage | 230V AC +10% / -15% @ 50/60 Hz | ||||
System Voltage | 24V DC (Nominal) | ||||
Zone Voltage | 21V DC (Nominal) | ||||
Sounder Alarm Output | 2 x 150mA @ 24V DC | 4 x 150mA @ 24V DC | |||
Fire Relay | 1 x Volt Free Relay, SELV @ 1A Max | ||||
Fault Relay | 1 x Volt Free Relay, SELV @ 1A Max | ||||
Zone Capacity | 32 devices per zone | ||||
Remote sounder operation | Via N/O contact connected to Class Change | ||||
Sounder Activation Delay | 0 to 10 minutes in 1 minute increments | ||||
Zone End of line | 1N4002 Diode (Cathode Stripe to Zone +ve) | ||||
Sounder End of Line | 10K resistor | ||||
Charger Voltage | 27.6V | ||||
Battery cut off | Battery voltage less than 20V | ||||
Battery Internal Resistance limit | 0.9 ohm | ||||
Enclosure size | 371 x 302 x 93 (mm) | ||||
Weight | 3 kg (Excluding Batteries) | ||||
Maximum battery space | 2 x 3.4 Ah, 12 Vdc sealed lead acid |