No products in the cart.
VERTIV (Emerson) Liebert HIPULSE-U 80KVA Online UPS
৳ 1,900,000.00
Need Pre-Order, Delivery Within 40 Working Days
Attain high availability without compromising efficiency
Investment free capacity up gradation only external cable is needed
No need of costly load bank to test the unit at site
Wide voltage & frequency range ensure UPS always run on utility power, prolong battery life.
Scale up availability by connecting to two independent sources to UPS
Achieve high system reliability with self-protection and fault diagnosis
Provide 12% more active power (kW) than conventional architecture based UPS Initiate prompt alarm upon leading loads detection
High fault tolerant design
Gradually stepping up load on generator thereby allows trouble free connection
Suitable to adapt as per today’s dynamic electrical environment
Concurrently supports multiple communication option
Features
Up to 98% operating efficiency in Eco-Mode operation. Up to 93% operating efficiency in double conversion mode.
Standard built in LBS function and smart parallel
REGEN mode of operation
Wide voltage and frequency range
Dual main input
Space vector PWM technology in IGBT switching (SVPWM) at inverter level
Strong 0.9 output PF loading capacity
Leading power factor loads detection
High input fault currently capability
Power walk-in enabled
Compatible to 1+N and N+1 configuration
Two independent intellislots to achieve multi channel data highway
VERTIV Liebert HIPULSE-U, Emerson Liebert HIPULSE-U
Brand | VERTIV(Ex Emerson) |
Model | Hipulse U |
Country of origin | USA |
Country of manufacture | India |
Nominal Rating | 80 KVA/72KW |
Rectifier type | 6p |
Input | |
Nominal input voltage | 380/400/415Vac 3-wire plus Ground |
Input Voltage Range | 290 to 498 Vac |
Nominal input frequncy | 50/60HZ |
Input frequency range | 45-55HZ/55-65HZ |
Input current distortion With | 5% With optional filter |
Power factor (with filter) | 0.9 with optional filter |
Output | |
Nominal output valtage | 380/400/415Vac 3- phase with Neutral |
Frequency | |
Voltage stability | ± 1% (Steady state), ± 5% (Transient state) |
Transient recovery time | 20 milliseconds to 1% |
Frequncy stability | ± 0.1% (synchronized with internal clock), ±6% (max) (syncchronized with bypass) |
Overload capability | 101-110%,60minutes;125-150%,1 minute |
Voltage distortion with linear load | <1% |
Voltage distortion with 100% non- linear load | < 5% |
permissible load unbalance | 100% |
Non linear load capability | 100% |
Load handing capability without kVA derating | 0.5 lagging to 0.9 leading |
Phase angle displacement accuracy | |
100% balalance load | ±1° |
100% unbalance load | ±1° |
Isolation Transformer | Built -in |
Battery | |
Battery Brand | LEOCH/Emerson approved Battery |
Battery capacity | 12 V,80 AH |
Number of Battery | 34 |
Back Up time | Standard backup |
Dimensions and weight | |
Depth (mm) | 855 |
width(mm) | 900 |
Height(mm) | 1900 |
width (kg) | 900 Kg |
General | |
General and safety requirements for UPS | IEC 62040-1-1 |
EMC requirements for UPS | IEC 62040-2 |
Desing & Test Methods (1999) | IEC 62040-3 |